BELT DRIVEN BACKWARD CENTRIFUGAL IN SOUNDPROOF CABINET 400ºC/2H
MANUFACTURING FEATURES:
• range fans assembled in soundproof cabinets with insulated panels.
• Fan assembled on antivibration mountings.
• Simple inlet, backward impeller with self-cleaning system.
• Supplied with motor, pulleys and belts.
• Gland connection included.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230/400V 50Hz in three phase motors up to 4kW and 400/690V 50Hz for higher powers.
APPLICATIONS:
Designed for inline installation, indoor or outdoor assembly, they are suitable for:
• Air renewal in buildings and industries.
• Smoke emergency exhaust with motor outside the hazardous area (400ºC/2h certified).
• Industrial and professional kitchen hoods.
• Maximum working temperature: carried air 130ºC; environment 60ºC.
UNDER REQUEST:
• Special voltages.
• 2 speed motors.
• Orentation:
- LG90 (horizontal).
- LG0 (vertical outlet).
Official homologation by the European laboratory APPLUS according to EN 12101-3:2015
Certification Nr: 0370-CPR-1371
A | B | C | D | D1 | E | F | G | G1 | H | I | J | J1 | K | L | M | N | O | ØR | P | Q | S | T | U | V | W |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
1988 | 1488 | 912 | 1326,8 | 503 | 1383,7 | 805 | 1259,7 | 435,9 | 1316,7 | 740 | 1319 | 495,5 | 1060 | 1874,5 | 1109 | 111 | 475,8 | 708 | 40,5 | 60 | 545 | 878 | 100 | 899 | 479 |