AJ
Model
AJ 355 T2 UN CONFORT
Code

AJ 355 T2 UN CONFORT

CIRCULAR AXIAL JET FAN CONFORT

MANUFACTURING FEATURES:

The AJ models are composed of an axial fan and two silencers.

FAN:
•Axial fan with reinforced tubular casing, made of steel sheet. The connection box is accessible by the side from a removable door.
•Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Standard voltages 230/400V 50Hz for 1 speed motors and 400V 50Hz for 2 speed fans

SILENCERS:

•Casing in galvanized steel. Inner duct made of perforated galvanized steel sheet.
•The silencers are filled with mineral wool with high acoustic absorption properties, preventing most of the fan noise to be propagated.
•Unidirectional AJ UN is equipped with a protection guard at the inlet side and a deflector at the outlet. The deflector directs the air away from the ceiling and obstacles like beams or ducting, sweeping the whole volume of air to the closest extraction point.
•Reversible AJ RE is equipped with protection guards on both sides.

APPLICATIONS:

•Conceived for car parkings and large spaces where polluted air, needs to be removed effectively.
•An optimized design minimizes the height needed for their installation and assures a silent operation.
•Maximum working temperature: 60ºC.

 

Fan

Max flow
5240 m³/h
Weight
99 Kg

Motor

Power
0,55 kW
RPM Motor
2780
I max. 400 V
1,36
Weight
12 Kg
AJ 355 T2 UN CONFORT
Loading...
Design point
Loading...
Service point
Loading...
Alternative point

AJ 355 T2 UN CONFORT

Dimensions scheme
A B F G H I K L M O ØC ØD ØE Thrust (N)
1833,5 720 8x45º 393,5 455 122 461 411 345,5 M8 455 361 395 26

AJ 355 T2 UN CONFORT

Electrical scheme

AJ 355 T2 UN CONFORT

Model
INT 25 3P A
Code
Information
SAFETY SWITCH

MANUFACTURING FEATURES

• Safety start-stop switches according to IEC 60947-1 and IEC 60947-3.
• IP65 and always equipped an auxiliary contact.
• Useful for switching off the current before handling the fan.

*Máx. thermal current air (A)